Flowma Flowmasonic WUF 620 CF Series clamp-on transit-time ultrasonic flow meter utilizes transit-time principle. The Flowmasonic transducer is mounted outside surface of the pipe without requirements of flow stop or pipe cutting. It’s very simple, convenient for installation, calibration and maintenance.
Different sizes of transducers satisfy different measuring demand. Plus, select thermal energy measuring function to achieve completely energy analysis. It is widely applied in processing monitoring, water balance test, district heating balance test, energy efficiency monitoring as easy installation and simple operation advantages.
Flowmasonic WUF 620 CF Series Features
- 4 Lines Display Velocity, Flow Rate, Volume And Meter Status
- Clamp-on Mounted, Unnecessary Pipe Cutting Or Processing Interruption
- Acceptable Fluid Temperature Range -40°C~260°C
- Built-in Data Storage Is Optional
- Selecting Temperature Sensor PT1000 To Achieve Thermal Energy Measurement Function
- Suitable For DN20-DN6000 Flow Measurement By Selecting Different Size Transducers Bi-directional Measurement, Flow Range From 0.01m/s To 12m/s
When selecting a measurement site, it is important to select an area where the fluid flow profile is fully developed to guarantee a highly accurate measurement. Use the following guidelines to select a proper installation site:
- Choose a section of pipe that is always full of liquid, such as a vertical pipe with flow in the upward direction or a full horizontal pipe.
- Ensure enough straight pipe length at least equal to the figure shown below for the upstream and downstream transducers installation.
- Ensure that the pipe surface temperature at the measuring point is within the transducer temperature limits
- .Consider the inside condition of the pipe carefully. If possible, select a section of pipe where the inside is free of excessive corrosion or scaling.
Performance Index
Measuring Principle | Transit-time |
Velocity | 0.01 – 12 m/s, Bi-directional Measurement |
Resolution | 0.25mm/s |
Repeatability | 0.1% |
Accuracy | ±1.0% of Reading |
Response Time | 0.5s |
Sensitivity | 0.003m/s |
Damping | 0-99s(settable by user ) |
Suitable Fluid | Suitable Fluid Clean or tiny amounts of solids, air bubbles liquid , Turbidity<10000 ppm |
Power Supply | AC: 85-265V DC:12- 36V/500mA |
Installation | Wall Mounted |
Protection Class | IP66 |
Operating Temperature | to +75℃ |
Measuring Unit | meter,ft,m³,liter,ft³,gallon,barrel etc. |
Communication Output | 4~20mA, OCT, Relay, RS485 (Modbus-RUT), Data Logger ,GPRS |
Energy Unit | Unit : GJ,Opt: KWh |
Security | Keypad Lockout, System Lockout |
Size | 244*196*114mm |
WB4:C22eight | 2.4kg |