Flowmasonic

Fire Pump Test Meter
Fire Pump Test Meter

Fire Pump Test Meter

4 minutes, 1 second Read

Fire pump test meter manufactured by Gerand Engineering Co. was required to supply Factory Mutual all drawings and independent laboratory test reports on all venturi in order to apply for Factory Mutual approval.

The Factory Mutual Approval was issued to Gerand Engineering Co. after the units were tested and met the Approval Standard – Class No. 1046 for Fire Pump Flowmeter Systems.

Stated in this standard under II Description, Para. 4.2 Accuracy is that the system must meet an accuracy of ±2%, full-scale deflection for the range of flows from 50% to 200% of the rated capacity of the pump for which it is used.

Gerand pump test flow meter

Factory Mutual annually conducts a stringent audit and inspection of all designs and parts used in the Fire Pump Test Meters. This inspection includes the reviewal of all quality control information we maintain on each part as well as a physical measurement of all dimensions of parts and random testing of the gauges.

Attached to the meter with a brass chain is an oblong metal tag with the suggested piping diagram of the system on one side and the following operating instructions on the reverse side:

  1. Close system OSY valve “A”
  2. Open by-pass valve and “B” butterfly throttle valve
  3. Purge meter, located on venturi, as follows:
    • Open station shut-off valves on venturi, and vent valves attached to the meter. When a steady stream of water without air bubbles passes through the clear plastic hoses, the meter is purged of air.
    • Close the vent valves after purging.
  4. Start the fire pump, and read the meter in GPM.
  5. Refer to the pump GPM requirement and adjust the throttle valve to meet the requirement.
  6. After the test, open valve “A” and close the by-pass and “B” valves.

More information please click  catalog gerand pump test meter


Sebagai informasi flow meter yang banyak di pakai di industri mempunyai jenis yang berbeda beda tergantung jenis cairan, sistem instalasi sera tingkat akurasinya dan berikut ini jenis jenis serta model flow meter :

Flow Meter Portable

  • Flow meter portable mulai terkenal saat dikenalkanya flow meter jenis ultrasonic dimana cara penggunaan dan instalasinya cukup mudah dan cepat serta  dapat dibawah kemana mana.
  • Portable flowmeter ini menggunakan jenis clamp on flow meter dimana sensor atau sering di sebut dengan transducer ultrasonic cukup di clamp pada permukaan luar pipa, Karena prosesn insatlasi tanpa memotong pipa atau melubangi pipa maka biaya instalasi dari flow meter clamp on sangat murah dan cepat.
  • Untuk jenis flow meter portable biasanya di lengkapi dengan data logger vaik itu secara internal maupun external dan untuk power karena sifatnya portable biasanya menggunakan battery yang bisa di charge dan umumnya battery mampu bekerja pada waktu cukup lama diatas 5 jam.
  • Info lebih lanjut product portable flow meter silahkan click

Clamp on Ultrasonic Flow Meter

  • Flowmeter ultrasonic merupakan tipe flow meter yang cara kerjanya mengukur kecepatan aliran fluida dengan menggunakan ultrasound sehingga dengan perhitungan volume yang mengalir bisa terbaca di transmitter ultrasonic.
  • Dengan menggunakan sensor ultrasonik atau sering disebut transducer ultrasonic flowmeter dapat mengukur kecepatan rata dari aliran fluida dalam pipa dengan cara mengukur rata rata perbedaan waktu antara waktu pengiriman signal dan penerimaan signal dengan arah aliran.
  • Info lebih lanjut product clamp on ultrasonic flowmeter silahkan click

Flowmeter Mass Flow Coriolis

  • Flowmeter coriolis adalah jenis flow meter yang secara teori menghitung kekuatan gaya/tenaga akibat adanya osilasi suatu sensor yang dilewati cairan dengan menggunakan perhitungan coriolis yang di konversi ke suatu aliran massa.
  • Coriolis flow meter secara real mempu menghitung massa aliran sehingga perubahan temperature dari aliran tidak banyak berpengaruh. Begitu juga persolan perubahan aliran karena instalasi atau sebab lain yang berakibat aliran tidak laminer serta terjebaknya udara atau gas dalam aliran tidak memeengaruhi akurasi. Berbeda dengan sifat flow meter yang menghitung volume dimana mass flow meter bisa mengabaikan berat dari udara atau gas yang terjebak dalam aliran.
  • Info lebih lanjut product  coriolis mass flow meter silahkan click

Flow Meter Electromagnetic

  • Flowmeter electromagnetin yang sering disebut magnetic flow meter atau magmeter merupakan jenis flow meter yang cara kerjanya menggunakan hukum faraday. Karena sifat kerjanya seperti itu maka magnetic flow meter hanya bisa kerja pada cairan yang mempunyai konduktifitas pada tingkatan tertentu dan umumnya pada kisaran minimal 20 micro siemens
  • Info lebih lanjut product  Electromagnetic flow meter silahkan click 

Turbine Flow Meter

Vortex Flow Meter

Positive Displacement Flow Meter

Variable Area Flow Meter

Insertion Flow Meter

Flow Meter Open Channel 

  • Open channel flow meter adlah flow meter yang dapat diaplikasikan untuk mengukur aliran pada sistem saluran terbuka seperti pada kanal, sungai atau parit.
  • Pada dasrnya flow meter open chanel ini menghitung kecepatan aliran dengan mempertimbangkan ketinggian permukaan. Untuk pengukuran kecepatan aliran bisa menggunakan transittime flow meter atau Magnetic flow meter. Sedangkan untuk ketinggian permukaan aliran menggunakan ultrasonic level sensor
  • Penggabungan velociti dengan luas penampang bisa menghasilkan kapasitas aliran atau flow rate aliran dalam kanal.
  • Info lebih lanjut product  Open Channel Flow Meter silahkan click 
Info : marketing@wmablog.com

 

Similar Posts

Skip to content