ONICON F-1000 Series Inline & Insertion Turbine Flow Meter
ONICON F-1000 Series Inline & Insertion Turbine Flow Meter

ONICON F-1000 Series Inline & Insertion Turbine Flow Meter

3 minutes, 7 seconds Read

ONICON’s F-1000 Series is a family of insertion and inline style turbine meters flow meters that provide accurate, reliable flow measurement in a variety of applications. The F-1000 Series meters are suitable for use in pipes ranging in size from ¾ to 72” in diameter.

Each model utilizes ONICON’s patented electronic turbine rotation sensing system and unique low mass turbine design that is accurate over wide flow ranges with excellent low flow measurement capability

Features

• The Dual Turbine Advantage

Dual counter-rotating turbines with mirrored helixes reduce the effects of the most common type of flow distortion, the swirl caused by bends and elbows. This reduces the upstream straight run requirements in some applications.

• Programmable with Built-in Diagnostics

The USB interface makes field programming simple. Advanced diagnostics provide real-time data from the meter

.• Excellent Long-term Reliability

Patented electronic sensing is resistant to scale and particulate matter. Low mass turbines with engineered jewel-bearing systems provide a mechanical system that virtually does not wear.

• Simplified Hot Tap Insertion Design

Allows for insertion and removal by hand without system shut-down for insertion meters

.• Unmatched Price vs. Performance

Individually wet-calibrated, highly accurate instrumentation at very competitive prices.

Applications

  • Chilled water or hot water & water/glycol solutions for HVAC
  • Domestic/municipal water
  • Clean process water

Specifications

Accuracy ± 0.5% of reading at the calibrated velocity
Insertion ± 1% of reading from 3 to 30 ft/s (10:1 range
± 2% of reading from 0.4 to 20 ft/s (50:1 range)
Inline ± 2% of reading from 0.8 to 38 GPM (50:1 range)
Pipe Size Range Insertion 1¼ through 72” nominal diameter
Inline Threaded or sweat union fittings – ¾ or 1”
Supply Voltage 24 ±4 V AC/DC at 100 mA
Liquid Temperature Range Medium Temp 150° F continuous, 200° F peak
High Temp 280° F continuous, 300° F peak
Meters operating above 250° F require 316 SS construction option
Ambient Temperature Range -5° to 160° F (-20° to 70° C)
Operating Pressure 400 PSI maximum
Pressure Drop Insertion Less than 1 PSI at 20 ft/s in 1½” pipe, decreasing in larger pipes and lower velocities
Inline 3 PSI at a maximum flow rate
Material Wetted material Electroless nickel plated brass stem
Optional 316 stainless steel, NSF/ANSI 61/372 version*
Output Signal Available Frequency Output 0-15 V peak pulse, programmable max Hz
Closing time Scaled Pulse / Alarm Output Isolated solid-state dry contact
Contact rating: 100 mA, 50 VContact duration: Field programmable; 50, 100, 500 or 1000 ms
Opening time Analog Output (non-isolated) Signal type: 4-20 mA, 0-10 V or 0-5 V (jumper selectable)Output range: Field programmable
Pressure ports Isolated Analog Output Signal type: 4-20 mA, 0-10 V or 0-5 V (jumper selectable)
Output range: Field programmable
Electronics Enclosure NEMA4 enclosure
Optional Submersible enclosure
Electrical Connections Standard 10’ of cable with ½” NPT conduit connection
Optional Indoor DIN connector with 10’ of plenum rated cable

CALIBRATION

Every F-1000 series meter is wet-calibrated using N.I.S.T.1 traceable standards. A certificate of calibration is provided with each meter.

THREE DIFFERENT OUTPUT VERSIONS

Frequency & Scaled Pulse/Alarm Outputs

This version provides a high-resolution frequency output and a scaled pulse output for totalizing flow. The frequency output allows for connection to ONICON Btu meters or displays. The scaled pulse output may also be configured as an alarm.

Frequency, Analog & Scaled Pulse/Alarm Outputs

This version provides a high-resolution frequency output, an analog output for flow rate and a scaled pulse output for totalizing flow. The frequency output allows for connection to ONICON Btu meters or displays. The scaled pulse output may also be configured as an alarm.

Frequency, Isolated Analog & Scaled Pulse/Alarm Outputs

This version provides a high-resolution frequency output, an isolated analog output for flow rate and a scaled pulse output for totalizing flow. The frequency output allows for connection to ONICON Btu meters or displays. The scaled pulse output may also be configured as an alarm.

Data Sheet ONICON F-1000 Series Turbine Flow Meter

 