Flowmasonic

Dwyer Series MFS2 Magnetic Inductive Flow Sensor
Dwyer Series MFS2 Magnetic Inductive Flow Sensor

Dwyer Series MFS2 Magnetic Inductive Flow Sensor

1 minute, 59 seconds Read

Dwyer Series MFS2 Magnetic Inductive Flow Sensor is a compact, lower-cost plastic alternative to the Series MFS. Unlike sensors with moving parts, the MFS2 can be used in applications dealing with contaminated media.

This series provides a reliable measuring technique, an obstruction-free pipe cross-section, as well as a quick response time, making this series ideal for interference-free operation. Any change in temperature, density, viscosity, concentration, or electrical conductivity of the liquid, does not affect the output signal of this Magnetic Inductive Flow Sensor. This, in addition to its long life cycle and PVDF process connection, makes this series perfect for accurate reversible gauging of the volume flow of conductive liquids in closed piping.

The measuring pipe is in a magnetic field. If an electrically conductive medium with a certain flow passes through the pipe, it passes at a right-angle to the magnetic field, creating a voltage that is proportional to the average flow velocity and picked up by two electrodes within the MFS2. A frequency output signal is obtained that is proportional to the flow (analog output option available).

Dwyer Series MFS2 Features

  • No moving parts
  • No mechanical wear
  • Maintenance-free
  • Can be applied in applications dealing with contaminated media with no mechanical component in the flow
  • Obstruction free pipe cross-section yields low-pressure drop
  • Unaffected by a change in temperature, density, viscosity or concentration

Application

  • Continuous flow monitoring
  • The flow of conductive liquids
  • Water & wastewater treatment
  • Industrial systems
  • Irrigation applications
Another Article:

Specification

Service Compatible, non-coating, conductive liquids.
Wetted Materials >Grounding Rings and Electrodes: 316 SS;
Process Connections: PVDF;
O-rings: EPDM.
Accuracy ±1% of reading.
Repeatability 1%.
Temperature Limits >Process: 14 to 140°F (-10 to 60°C);
Ambient: 41 to 140°F (5 to 60°C).
Pressure Limits >145 psi (10 bar) @ 68°F (20°C);
116 psi (8 bar) @ 104°F (40°C);
87 psi (6 bar) @ 140°F (60°C).
Response Time < 100 ms.
Power Requirements 24 VDC ±15%.
Power Consumption 0.6 W.
Output Frequency: Square-wave, NPN or PNP.
Flow Indication LED green, flow proportional blinking.
Enclosure Rating IP65.
Enclosure Material ABS plastic.
Electrical Connection Plug connector M12x1.
Conductivity > 20 µS/cm min.
Weight >MFS2-1, -2, -3, -4, -5: 8 oz (226.8 g);
MFS2-6: 1 lb (0.45 kg).
Agency Approvals CE.

Ref: dwyer-inst.com

Download Data Sheet: Series MFS2 Magnetic In-Line Inductive Flow Sensor

Similar Posts

Skip to content